TY - JOUR
T1 - Performance and design analyses of various configurations of dew point evaporative cooling-based desiccant air-conditioning (DAC) systems for hot and humid conditions
AU - Lao, Marco
AU - Lin, Jie
AU - Miksik, Frantisek
AU - Thu, Kyaw
AU - Miyazaki, Takahiko
N1 - Funding Information:
The authors would like to acknowledge the Philippine Atmospheric, Geophysical and Astronomical Services Administration (PAGASA) of the Department of Science and Technology of the Philippines for the climate data.
Funding Information:
This study was funded by the Science Education Institute of the Department of Science and Technology (DOST-SEI) of the Philippines.
Publisher Copyright:
© 2022, The Author(s).
PY - 2022/12
Y1 - 2022/12
N2 - Thermally driven desiccant- and evaporative cooling-based technologies are promising greener and cheaper alternatives to compressor-based systems due to the separate handling of latent and sensible loads. Desiccant air-conditioning (DAC) systems comprise a desiccant dehumidifier, a sensible cooling unit, a heat source for regeneration, and a heat recovery unit. These components of a DAC system can be arranged in various ways to give different configurations with varying advantages and disadvantages. In this study, five configurations of thermally driven desiccant dehumidifier- and dew point evaporative cooling (DPEC)-based DAC systems were investigated. Seven evaluation criteria namely regeneration temperature, desiccant moisture removal capacity, COPt, DPEC L/H, heat exchanger UA, system size, and fan power requirement were employed. Results show that the standard cycle in ventilation mode offers the highest COPt despite having the highest regeneration temperature. Recirculation of the return room air can operate at a significantly lower regeneration temperature at the expense of larger equipment size and much lower COPt. DAC with an internally cooled dehumidification can operate at low regeneration temperature at the expense of higher fan power and slightly lower COPt. Dividing the dehumidification process into two stages can offer operation at moderately lower regeneration temperature without severely affecting the other criteria. This study can serve as a guide for the selection of an appropriate DAC configuration for space cooling depending on the objective criteria and the resources available.
AB - Thermally driven desiccant- and evaporative cooling-based technologies are promising greener and cheaper alternatives to compressor-based systems due to the separate handling of latent and sensible loads. Desiccant air-conditioning (DAC) systems comprise a desiccant dehumidifier, a sensible cooling unit, a heat source for regeneration, and a heat recovery unit. These components of a DAC system can be arranged in various ways to give different configurations with varying advantages and disadvantages. In this study, five configurations of thermally driven desiccant dehumidifier- and dew point evaporative cooling (DPEC)-based DAC systems were investigated. Seven evaluation criteria namely regeneration temperature, desiccant moisture removal capacity, COPt, DPEC L/H, heat exchanger UA, system size, and fan power requirement were employed. Results show that the standard cycle in ventilation mode offers the highest COPt despite having the highest regeneration temperature. Recirculation of the return room air can operate at a significantly lower regeneration temperature at the expense of larger equipment size and much lower COPt. DAC with an internally cooled dehumidification can operate at low regeneration temperature at the expense of higher fan power and slightly lower COPt. Dividing the dehumidification process into two stages can offer operation at moderately lower regeneration temperature without severely affecting the other criteria. This study can serve as a guide for the selection of an appropriate DAC configuration for space cooling depending on the objective criteria and the resources available.
UR - http://www.scopus.com/inward/record.url?scp=85147574775&partnerID=8YFLogxK
UR - http://www.scopus.com/inward/citedby.url?scp=85147574775&partnerID=8YFLogxK
U2 - 10.1007/s44189-022-00011-7
DO - 10.1007/s44189-022-00011-7
M3 - Article
AN - SCOPUS:85147574775
SN - 2010-1325
VL - 30
JO - International Journal of Air-Conditioning and Refrigeration
JF - International Journal of Air-Conditioning and Refrigeration
IS - 1
M1 - 12
ER -