抄録
Performance analyses have been carried out for a heat pump cycle using zeotropic refrigerant mixtures of carbon dioxide (CO<Sub>2</Sub>) and dimethyl ether (DME). In order to clarify the characteristics and coefficient of performance (COP) of CO<Sub>2</Sub>/DME heat pump cycle, the concentration of mixture was varied over a wide range. The calculation conditions were established as a hot-water supply system and the calculations were conducted by considering the heat transfer between the refrigerant and heat source/sink water. Because the heat transfer between refrigerant and heat source/sink water strongly affects on the cycle behavior, effects of the heat transfer capability parameter were investigated. The heat pump cycle is formed around the critical point for high CO<Sub>2</Sub> concentration mixtures and it is formed under the critical point for low CO<Sub>2</Sub> concentration mixtures. The COP has the maximum at a certain pressure for each mixture and the COPs of the mixture and pure DME are higher than that of pure CO<Sub>2</Sub>. Operating pressure decreases with increase of DME concentration. The effects of heat transfer between the refrigerant and heat source/sink water on characteristics of the cycle have also been clarified.
| 寄稿の翻訳タイトル | Performance Analysis of heat pump cycle using CO<Sub>2</Sub>/DME refrigerant mixture |
|---|---|
| 本文言語 | 日本語 |
| ページ(範囲) | 245-252 |
| ページ数 | 8 |
| ジャーナル | 日本冷凍空調学会論文集 |
| 巻 | 26 |
| 号 | 3 |
| DOI | |
| 出版ステータス | 出版済み - 2009 |
フィンガープリント
「CO<Sub>2</Sub>/DME混合冷媒を用いたヒートポンプサイクルの性能解析」の研究トピックを掘り下げます。これらがまとまってユニークなフィンガープリントを構成します。引用スタイル
- APA
- Standard
- Harvard
- Vancouver
- Author
- BIBTEX
- RIS