TY - JOUR
T1 - Development of a slug flow absorber working with ammonia-water mixture
T2 - Part I - Flow characterization and experimental investigation
AU - Kim, H. Y.
AU - Saha, B. B.
AU - Koyama, S.
PY - 2003/8
Y1 - 2003/8
N2 - This study deals with an experimental investigation for a counter-current slug flow absorber, working with ammonia-water mixture, for significantly low solution flow rate conditions that are required for operating as the GAX (generator absorber heat exchanger) cycle. It is confirmed that the slug flow absorber operates well at the low solution flow rate conditions. From visualization results of the flow pattern, frost flow just after the gas inlet, followed by slug flow with well-shaped Taylor bubble, is observed, while dry patch on the tube wall are not observed. The liquid film at the slug flow region has smooth gas-liquid interface structure without apparent wavy motion. The local heat transfer rate is measured by varying main parameters, namely, ammonia gas flow rate, solution flow rate, ammonia concentration of inlet solution and coolant inlet conditions. The heat transfer rate while absorption is taking place is higher than that after absorption has ended. The absorption length is greatly influenced by varying main parameters, due to flow conditions and thermal conditions.
AB - This study deals with an experimental investigation for a counter-current slug flow absorber, working with ammonia-water mixture, for significantly low solution flow rate conditions that are required for operating as the GAX (generator absorber heat exchanger) cycle. It is confirmed that the slug flow absorber operates well at the low solution flow rate conditions. From visualization results of the flow pattern, frost flow just after the gas inlet, followed by slug flow with well-shaped Taylor bubble, is observed, while dry patch on the tube wall are not observed. The liquid film at the slug flow region has smooth gas-liquid interface structure without apparent wavy motion. The local heat transfer rate is measured by varying main parameters, namely, ammonia gas flow rate, solution flow rate, ammonia concentration of inlet solution and coolant inlet conditions. The heat transfer rate while absorption is taking place is higher than that after absorption has ended. The absorption length is greatly influenced by varying main parameters, due to flow conditions and thermal conditions.
UR - http://www.scopus.com/inward/record.url?scp=0038823959&partnerID=8YFLogxK
UR - http://www.scopus.com/inward/citedby.url?scp=0038823959&partnerID=8YFLogxK
U2 - 10.1016/S0140-7007(03)00020-3
DO - 10.1016/S0140-7007(03)00020-3
M3 - Article
AN - SCOPUS:0038823959
SN - 0140-7007
VL - 26
SP - 508
EP - 515
JO - International Journal of Refrigeration
JF - International Journal of Refrigeration
IS - 5
ER -