Correlation for forced convective boiling heat transfer of nonazeotropic refrigerant mixture of HCFC22/CFC114 in a horizontal smooth tube

Hiroshi Takamatsu, Satoru Momoki, Tetsu Fuju

Research output: Contribution to journalArticlepeer-review

Abstract

Experiments are carried out on the boiling heat transfer of nonazeotropic refrigerant mixtures of HCFC22/CFC114 flowing inside a 7.9 mm ID horizontal smooth tube. Using a water-heated, double-tube type evaporator, the local heat transfer coefficients are measured for both counter and parallel flows. An empirical correlation equation is proposed for the data in the annular-flow regime, taking into account the mixture effect in the authors' previous correlation equation for pure refrigerants. The mean deviation between the calculated and measured heat transfer coefficients is 8.9% for the present experimental data and 7.1% for the data obtained by Jung. The equation reveals that the convection heat transfer is dominant due to the suppression of nucleate boiling for the mixtures.

Original languageEnglish
Pages (from-to)3558-3563
Number of pages6
JournalInternational Journal of Heat and Mass Transfer
Volume36
Issue number14
Publication statusPublished - Sept 1 1993

All Science Journal Classification (ASJC) codes

  • Fluid Flow and Transfer Processes
  • Energy(all)
  • Mechanical Engineering

Fingerprint

Dive into the research topics of 'Correlation for forced convective boiling heat transfer of nonazeotropic refrigerant mixture of HCFC22/CFC114 in a horizontal smooth tube'. Together they form a unique fingerprint.

Cite this