インバータ駆動パッケージ空調機の現地性能検証のための簡易冷房能力推算方法の提案

Translated title of the contribution: A Proposal of Cooling Capacity Estimation method for Onsite Performance Verification of Inverter-drive Packaged Air Conditioners

万尾 達徳, 谷野 正幸, 石井 秀一, 小山 繁

    Research output: Contribution to journalArticlepeer-review

    Abstract

    We proposed an estimation method of cooling capacity, to realize the onsite performance verification conveniently without flow rate data of air and refrigerant, on inverter-drive packaged air conditioners. In this study, to evaluate possibility of proposed estimation method, the propriety of this estimation method was inspected using experimental equipment (Cooling capacity of 2.8kW). And then estimation values of cooling capacities were evaluated by comparison with measured values. As a result, it was confirmed that logics in this method is correct in behavior of the refrigeration system characteristics, and this method could estimate the cooling capacity of refrigeration system in about 8% of the precision.
    Translated title of the contributionA Proposal of Cooling Capacity Estimation method for Onsite Performance Verification of Inverter-drive Packaged Air Conditioners
    Original languageJapanese
    Pages (from-to)93-100
    Number of pages8
    JournalTransactions of the Society of Heating, Air-Conditioning and Sanitary Engineers of Japan
    Issue number146
    Publication statusPublished - May 5 2009

    Fingerprint

    Dive into the research topics of 'A Proposal of Cooling Capacity Estimation method for Onsite Performance Verification of Inverter-drive Packaged Air Conditioners'. Together they form a unique fingerprint.

    Cite this